7 Output Channels Protection Relay Test Set
In stock
Reconfirm the price with seller
- Courier
- In detail
Products of other enterprises
Description
Voltage generators | ||
Setting Range |
4-phase AC (L-N) | 4 x 0 ... 130 V |
2-phase AC (L-L) | 2 x 0 ... 260 V | |
Power | 4-phase AC (L-N) | 4 x 70VA, at 0 ... 130 V |
2-phase AC (L-L) | 2 x 140VA, at 0 ... 260 V | |
Accuracy | < 0.07% reading + 0.03% range guaranteed at 0-130V < 0.04% reading + 0.01% range typical at 0-130V |
|
Resolution | 1mV | |
Current generators | ||
Setting Range |
3-phase AC (L-N) | 3 x 0 ... 40 A |
1-phase AC (2L -N) | 1 x 0 ... 80 A | |
1-phase AC (3L-N) | 1 x 0 ... 120 A | |
Power | 3-phase AC (L-N) | 3 x 150 VA , at 0 ... 40A Max 250VA, with the other current channels unload |
1-phase AC (2L -N) | 1 x 300VA, at 0 ... 80A Max 450VA, with the other current channels unload | |
1-phase AC (3L-N) | 1 x 900 VA | |
Accuracy | < 0.14% reading + 0.06% range guaranteed at 0-40A < 0.05% reading + 0.02% range typical at 0-40A |
|
Resolution | 1mA | |
Generators, general | ||
Frequency | Range | 0 ... 1000 Hz |
Accuracy / drift | Error < 0.001Hz at 10 ... 65Hz, Error < 0.01Hz at 65Hz...450Hz Error < 0.02Hz at 450Hz...1000Hz |
|
Resolution | 0.001Hz | |
Phase | Range | - 360° ... +360° |
Accuracy / drift | Error < 0.2 ° | |
Resolution | 0.1° | |
Time | Range | 0 ... 999, 999.999s |
Accuracy / drift | Error< 0.1ms | |
Resolution | 1ms | |
DC generators | ||
Voltage ranges | 0 ... 300V/180VA | |
Current ranges | 0 ... 20A/300W | |
Accuracy | Error< 0.1% reading + 0.1% range guaranteed at 0… 300 V; Error < 0.1% reading + 0.1% range guaranteed at 0...20 A; |
|
Resolution | 1mA; 1 mV | |
Harmonic | ||
Harmonic superpose times | 2 ... 20 | |
Aux DC Supply | ||
Range | 0...300V/0.6A | |
Binary Inputs | ||
Number | 8 pairs | |
Compatible Voltage | 10V ... 250V DC | |
Binary outputs | ||
Number | 4 Pairs | |
Capacity | 250V/3A AC/DC | |
Synchronization | ||
Synchronization mode | GPS | |
Power supply | ||
Nominal input voltage | 220V± 10% VAC, 1-phase | |
Power | 1000VA | |
Nominal frequency | 50± 10% Hz | |
Environmental conditions | ||
Operation temperature | -5° C ...55 ° C | |
Storage temperature | -20° C ...75 ° C | |
Humidity range | 5 ... 90 %, non-condensing | |
Weight | 20KG | |
Dimensions | 460(D)× 140 (W)× 360 (H) mm | |
Interface | RJ45 , USB, RS232, PS/2, VGA | |
PC Connection | RJ45 |
Model | Channels | AC Outputs |
K1063i | 10 output channels | 6*30A/3*60A/4*300V |
K1066i | 13 output channels | 6*30A/3*60A/7*300V |
K1066 | 13 output channels | 6*20A/3*40A/7*130V |
K1066+ | 13 output channels, | 6*30A/3*60A/7*130V |
K1063 | 10 output channels | 6*20A/3*40A/4*130V |
K1036 | 10 output channels | 3*40A/7*130V |
K1040 | 7 output channels | 3*40A/4*130V |
K1030 | 7 output channels | 3*30A/4*130V |
Contact the seller
7 Output Channels Protection Relay Test Set
We recommend to see